Siemens Synco ZW775 V2.0 Commissioning Instructions page 18

Central communication unit
Table of Contents

Advertisement

Step
Section
9
4.3
(continued)
4.3.2
4.3.3
4.3.4
10
4.4
18/148
Siemens Building Technologies
HVAC Products
Description
Application [ Parameter Setting ]
Data points in the "Settings" operating page
Command sequence:
Settings
> Faults
*) The command sequences Local >Fault input 1...20 and the corresponding data points are displayed
only if e.g. data point "N.X2 = Digital" was parameterized via Extra configuration > Input identifier,
and e.g. data point "Fault input 2 = N.X2" via Extra configuration > Faults.
Command sequence:
Settings
> System
> Fault relay
> Texts
Data points in the "Time switches" operating page
Command sequence:
Time switches
> Time switch 1
> Time switch 2....3
Data points in the "Message receiver" operating page
Command sequence:
Message receiver
> Message receiver 1
Message receiver > Message receiver 2...4 > Send messages
*)
The command sequences and data points are displayed only if you preconfigured the data point
"Receiver type" (and other data points) via "Settings > Message receiver > Message
receiver 1".
Download parameter set
Finish central communication unit parameterization (Step 9) with "Write parameter
set". Parameterization can be offline.
Workflow:
1.
Establish a connection to the plant before selecting
2.
Select the data points you want to download.
3.
Right-click the parameter set (e.g.
Write parameter set
.
4.
Click
Write parameter set
5.
Check transmission: The "Transmission result" column must show OK.
Note:
Parameterization is not yet complete. Continue in application [ Popcard ]
"Commissioning mode = On".
Applications [ Parameter Setting ] and [ Popcard ] display the same data points in
the "Settings" operating page.
Commissioning instructions OZW775 V2.01
Recommended commissioning
> Local
> Central commun. unit
> Local *) > Fault input 1
> Fault input 2...20
> Fault relay 1
> Fault relay 2
> Send messages
> Holidays/special days
) to open the context menu and select
Standard(1)
to start the write process (writing progress is displayed).
Data points
Message triggering
Fault input 1
Limit value fault on
Limit value fault off
Fault status message delay
Fault acknowledgement
Fault priority
Message triggering
Text for: No fault
Text for: Fault
same as Fault input 1
Data points
Message triggering
Fault priority
Fault source
same as Fault relay 1
Name
Phone number
Data points
Monday
...
Sunday
same as Time switch 1
Data points
(time switch) Monday *)
...
(time switch) Sunday
(time switch) special day
Entry 1...16
same as Message receiver 1
Write parameter set
.
CE1C5663en
22.06.2012