Configure Web Server Ozw775 - Siemens Synco ZW775 V2.0 Commissioning Instructions

Central communication unit
Table of Contents

Advertisement

Setting values
Note
Ethernet
Note
Siemens Building Technologies
HVAC Products
IP address:
Subnet mask
DHCP server:
Lease time:
First issued IP address:
Last issued IP address:
Default gateway:
Preferred DNS server:
Alternate DNS server:
Domain name:
MAC address:
Web server OZW775 uses a static IP address. Select an IP address outside the DHCP
range (see First/Last issued IP address) for web server OZW775, e.g. 192.168.1.180.

7.2.4 Configure web server OZW775

You need a PC/laptop with ACS V5.02 installed to configure web server OZW775. For
configuration, web server and PC/laptop are connected via USB interface or service
interface OCI700.
Settings > Communication > Ethernet
• IP address:
• IP subnetwork address: 255.255.255.0 (subnet mask)
• Default gateway:
• DNS server 1:
• DNS server 2:
• UPnP localization:
You do not need to address DNS server 2 (used only in redundant systems).
Commissioning instructions OZW775 V2.01
Appendix
192.168.1.1
 Router address
255.255.255.0  IP subnet mask
On  Web server OZW775 does not support DHCP client
function. However, we recommend to still enable this func-
tion for PC clients and other devices on the LAN.
30 min  Validity
192.168.1.30  Start of IP address range for DHCP server
192.168.1.80  End of IP address range for DHCP server
192.168.1.1  The router often is a default gateway
(Blank) or DNS server 1
(Blank) or DNS server 2
(Blank) or domain for working group
(Blank) clients receive their static address
from the DHCP pool
192.168.1.180
192.168.1.1
195.186.1.1
(blank)
---
125/148
CE1C5663en
22.06.2012