Siemens Synco ZW775 V2.0 Commissioning Instructions page 130

Central communication unit
Table of Contents

Advertisement

Important note
Test, intranet
Web server 1...x
static IP addresses
Web server 1...x
domain names
130/148
Siemens Building Technologies
HVAC Products
Prerequisites for sending e-mails:
• Web server OZW775 is integrated properly in the network (IP address, IP
subnetwork address (subnet mask), default gateway, DNS server).
• Web server OZW775 is connected to the internal mail server
or
• Web server OZW775 is connected (from corporate network) to an external mail
2)
server
.
The Internet e-mail account is set up.
The DSL routers are configured and connected to the Internet.
• A receiver (or several) is/are configured in FB "Message receiver".
1)
If an internal mail server is available, contact the network administrator for e-mail address and access
data. If no internal mail server is available, contact the network administrator to find out if an external
mail server can be used.
2)
If you want to use an external mail server (Internet SMTP server), submit an application to the
network administrator.
The web server OZW775 does not support HTTPS (Hyper Text Transfer Protocol
Secure). The emails are sent unsecured and unencrypted, i.e. without:
SSL (Secure Sockets Layer)
TSL (Transport Layer Security)
"Authentication mail server = Yes" checks unsecured, unencrypted information in the
data points "User name" and "Password" from the mail server for each email traffic.
After configuration, you can reach web servers OZW775 on the corporate network.
http://10.11.11.150
http://10.xy.xy.xy
http://agency1.siemens.com
http://agencyx.siemens.com
Commissioning instructions OZW775 V2.01
Appendix
Network protocol for secure data transmission.
Protocol for encryption of data transmissions on the
Internet.
http://10.12.12.150
http://agency2.siemens.com
1)
CE1C5663en