___________________ Preface ___________________ Application and properties ___________________ SIMATIC NET LEDs and connectors ___________________ Installation, connecting up, commissioning S7-1200 - TeleControl CP 1243-1 ___________________ Configuration ___________________ Program blocks Operating Instructions ___________________ Diagnostics and upkeep ___________________ Technical data ___________________ Approvals ___________________ Dimension drawings...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Hardware product version 2 Firmware version V3.0 The CP 1243-1 is the communications processor for connecting the SIMATIC S7-1200 to control center systems via the public infrastructure (e.g. DSL). With the help of VPN technology and the firewall, the CP allows protected access to the S7-1200.
Page 4
You will find the MAC address under the lower hinged cover of the housing. Product names and abbreviations ● CP / submodule / module These abbreviations are used below instead of the full product name CP 1243-1: ● TCSB This abbreviation ill be used below for the "TeleControl Server Basic", version V3.
Page 5
Preface Replaced manual issue Edition 12/2016 Current manual release on the Internet You will find the current version of this manual on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/man) Required experience To install, commission and operate the CP, you require experience in the following areas: ●...
Page 6
Siemens contact. Keep to the local regulations. You will find information on returning the product on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/109479891) Training, Service &...
Installing, connecting up and commissioning ................. 34 Note on operation ........................36 Configuration ............................37 Security recommendations ..................... 37 Configuration in STEP 7 ......................40 Addressing and authentication ....................41 4.3.1 TeleControl Basic ........................41 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 8
Data point configuration ......................82 4.10.2 Syntax of the data point names ..................... 88 4.10.3 Datapoint types ........................89 4.10.4 Configuration of the data point index ..................94 4.10.5 Status IDs of the data points ....................95 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 9
Processing status of e-mails ....................126 Downloading firmware ......................129 Module replacement ......................132 Technical data ............................ 133 Technical specifications of the CP 1243-1................133 Pinout of the Ethernet interface .................... 134 Approvals ............................135 Dimension drawings ..........................139 Documentation references ........................141 Index..............................
You will find the requirements and functions in the section E-mail configuration (Page 69). ● S7 communication and PG/OP communication with the following functions: – PUT/GET as client and server for data exchange with S7 stations – PG functions – Operator control and monitoring functions (HMI) CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
– After a request by the master or an OPC client connected to TCSB – Unsolicited, triggered by various selectable criteria ● Analog value processing Analog values can be preprocessed on the CP according to various methods. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● Data espionage ● Data manipulation ● Unauthorized access Secure underlying networks can be operated via additional Ethernet/PROFINET interfaces of the CPU. The security functions can be used independently of telecontrol communication. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 14
To allow monitoring, events can be stored in log files that can be read out using the configuration tool or can be sent automatically to a Syslog server. ● STARTTLS / SMTPS For the secure transfer of e-mails ● NTP (secure) For secure transfer during time-of-day synchronization CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
– To up to four non-redundant or redundant IEC masters With the Telecontrol Basic protocol, in addition to this, inter-station communication with up to 15 S7 stations with a CP 1243-1 can be operated via the telecontrol server. CP 1243-1...
Page 16
● Sending of up to 10 messages (e-mails) can be configured with the message editor. ● Sending e-mails via the TMAIL_C program block IPsec tunnel (VPN) Up to 8 IPsec terminals can be established for secure communication with other security modules. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● Maximum 128 rules with limitation of the transmission speed ("Bandwidth limitation") Configuration examples 1.6.1 Sending e-mails Configuration with sending of e-mails: The following example shows a configuration with sending of e-mails. The telecontrol communication of the CP is dsiabled. Figure 1-1 Sending e-mails CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The telecontrol server monitors the connections established by the remote stations. ● Inter-station communication Stations of the same type, for example S7-1200 with CP 1243-1, can communicate with each other by sending the frames via the telecontrol server. CP 1243-1...
Page 19
Telecontrol with a redundant master station (TCSB) The following figure shows a possible configuration with S7 stations communicating with a redundant master station (TCSB). Figure 1-3 S7 station communication with a redundant a master station CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
1 IP subnet. In this example, the DNP3 protocol is used; in other words, the stations are equipped with a CP 1243-1. A configuration in which the IEC protocol is used would have the same setup.
As an alternative to the router SCALANCE 812, you can also use a standard DSL modem and establish the VPN connection with a security module SCALANCE S. Addressing Refer to the information in the section DNP3 / IEC (Page 41). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Configuration example with a redundant DNP3 master station Addressing of the redundant DNP3 master The two devices of the redundant DNP3 master in the control center are addressed by the CP using one DNP3 address but two different IP addresses. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Engineering station with STEP 7 1.7.2 Software requirements Software for configuration and online functions To configure and use the CP, the following configuration tool is required: ● STEP 7 Basic / Professional V14.0 SP1 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 24
Application and properties 1.7 Requirements for use CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Open the upper or lower cover of the housing by pulling it down or up as shown by the arrows in the illustration. The covers extend beyond the housing to give you a grip. Figure 2-1 Opening the covers of the housing CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
LED colors and illustration of the LED statuses The LED symbols in the following tables have the following significance: Table 2- 3 Meaning of the LED symbols Symbol LED status ON (steady light) Flashing Not relevant CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 27
Running (RUN) without serious error green Partner not connected • Firmware loaded successfully • flashing green Starting up • Module fault • flashing red Invalid STEP 7 project data • Error loading firmware flashing red-green CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 28
IP address being obtained. • No connection to Industrial Ethernet Connection to communications partners Connection established to at least one partner green Partner reachable, CPU in STOP mode green Partner not reachable flashing green CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 29
No VPN connection configured on the CP Loading firmware Loading firmware. The DIAG LED flashes alternating red and green. Firmware was successfully loaded. flashing green Error loading firmware flashing red CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The Ethernet connector is located behind the lower hinged cover of the module. The interface is an RJ-45 jack according to IEEE 802.3. The pin assignment and other data relating to the Ethernet interface can be found in the section Technical data (Page 133). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
3.1.1 Notices on use in hazardous areas WARNING EXPLOSION HAZARD DO NOT OPEN WHEN ENERGIZED. WARNING The device may only be operated in an environment with pollution degree 1 or 2 (see IEC 60664-1). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
80 °C, special precautions must be taken. If the equipment is operated in an air ambient in excess of 50 °C, only use cables with admitted maximum operating temperature of at least 80 °C. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The equipment is intended to be installed within an ultimate enclosure. The inner service temperature of the enclosure corresponds to the ambient temperature of the module. Use installation wiring connections with admitted maximum operating temperature of at least 30 ºC higher than maximum ambient temperature. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Turning off the station when plugging/pulling the module Before pulling or plugging the module, always turn off the power supply to the station. Dimensions for installation Figure 3-1 Dimensions for installation of the S7-1200 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 35
30 mm 15 mm faces (examples) CP 1242-7, CP 1243-1, CP 1243-7, CP 1243-8 IRC 30 mm 15 mm * Width B: The distance between the edge of the housing and the center of the hole in the DIN rail mounting clip You will find detailed dimensions of the module in the section Dimension drawings (Page 139).
Close the front covers of the module and keep them closed during operation. Note on operation NOTICE Closing the front panels To ensure interference-free operation, keep the front panels of the module closed during operation. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● Keep the firmware up to date. Check regularly for security updates of the firmware and use them. ● Check regularly for new features on the Siemens Internet pages. – Here you will find information on network security: Link: (http://www.siemens.com/industrialsecurity) –...
Page 38
– The NTP protocol provides a secure alternative with NTP (secure) if you do not use telecontrol communication. – The HTTP protocol provides a secure alternative with HTTPS when accessing the Web server (configuration of the CPU). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 39
Closed Open after configuration SNMP 161 (UDP) Open Open after configuration Yes (with SNMPv3) * For information on avoiding opening the port during diagnostics, see section Online security diagnostics via port 8448 (Page 123). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
When you load the station, the project data of the station including the configuration data of the CP is stored on the CPU. You will find information on loading the station in the STEP 7 information system. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● Address of the master – IP address – Name that can be resolved with DNS If you use DNS, there must be a DNS server (see below) and this must be reachable for the CP. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Recommendation for setting the time Synchronization with a external clock at intervals of approximately 10 seconds is recommended. This achieves as small a deviation as possible between the internal time and the absolute time. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 43
Here you create the configuration under the following conditions: – Telecontrol communication is disabled. – The security functions are disabled. ● Security Here you create the configuration under the following condition: – The security functions are enabled. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 44
Only this option can be configured actively for the CPU: ● Time from CP The CPU adopts the time of day from a CP of the station if time forwarding from the CP to the CPU is enabled (see below). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
– TeleControl Basic – DNP3 – IEC 60870-5 Note that if you change the telecontrol communication type later, all specific parameters are deleted. These also include data point and partner information among other things. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The station address is the “common address of the ASDU" or the address of the information object. Entry of the station address (digits only). Permitted range of values: 1...65534. 4.6.2 Time-of-day synchronization Time-of-day synchronization For the configuration of the time-of-day synchronization read the section Time-of-day synchronization (Page 42). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The monitoring time is configured for the Ethernet interface as a global setting for all TCP connections. – The parameter below "Partner stations" As with the TCP connection monitoring time, the value of "Partner stations" can be adapted for each partner individually. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
CP and telecontrol server after which the CP sends a watchdog frame to the telecontrol server. The watchdog cycle is only configured with TCSB (parameter "Keepalive monitoring time"). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Permitted range: 0 ... 255 Default setting: 0 If you enter 0 (zero), the function is disabled. ● Connection confirmation Condition for the CP to request a connection confirmation from the master (never, always, only with segmented frames). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 50
Selection of an event class in which only the last current values are stored in the send buffer. In the default setting all values of events of classes 1 and 2 are stored in the send buffer, of class 3 only the current values (image memory procedure). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Settings on the master When configuring the monitoring times t and t make sure that you make the corresponding settings on the master so that there are no unwanted error messages or connection aborts. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 52
Maximum number of received data frames (I-APDUs), after which the oldest frame received from the master must be acknowledged. Permitted range: 1..8 Default setting: 8 The value must be less than the value of "Difference between send and receive sequence number" (k). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Read and write access private *) Note the use of lowercase letters! ● SNMPv3 Available only when security functions are enabled For information on the configuring SNMPv3, refer to the section SNMP (Page 70). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
By enabling the option the master that can then be configured is enabled for communication. ● Partner number The partner number is assigned by the system. It is required during data point configuration to assign data points to their communications partners. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 55
The value set here for the partner overwrites the global value that was set in the "Ethernet interface (X1) > Advanced options > TCP connection monitoring" parameter group. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 56
In the "Permanent" connection mode, there is a permanent connection to the communications partner. The CP only supports this connection mode. ● Connection establishment Specifies the communications partner that establishes the connection (always the CP). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
IP address of the TCSB server PCs (internal network). Only the public IP address is reachable from the Internet. The station does not therefore receive any information telling it which of the two computers of the redundancy group it is connected to. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Here, enter the project number of the CP in the partner station. (Parameter group "Security > CP identification" on the partner) Station Here, enter the station number of the CP in the partner station. (Parameter group "Security > CP identification" on the partner) CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The selection of the level used by the DNP3 CP which must correspond to that of the connected master is set separately in STEP 7 for each individual communications partner (DNP3 master). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 60
Using the first three parameters you specify the CPU access by the CP in the CPU scan cycle. You will find the structure of the CPU scan cycle in the section Read cycle (Page 96). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 61
CP time of day ● CP time to CPU Using this function, the CP can make its time of day available to the CPU. You will find details in the STEP 7 information system. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 62
PLC tag (data type DTL) for the date on which the CP was last unable to log in to the telecontrol server. ● TeleService status The PLC tag (BOOL) indicates whether a TeleService session is active. – 0 = No TeleService session active – 1 = TeleService session active CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● E-mail configuration See section E-mail configuration (Page 69). ● Log settings Here you make the settings for logging events relevant for security. See section Log settings - Filtering of the system events (Page 70). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The parameter of the type DWORD is allocated as follows: – Bits 0 - 7: Slot – Bits 8 to 20: Station number – Bits 21 to 31: Project number CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
CP and sent to the master for further evaluation. Range of values: – Do not send security statistics – Send security statistics Default setting: Do not send security statistics CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 66
If the configured number of statistics queries of the master is exceeded within the key exchange interval, the CP enters a message in the diagnostics buffer of the CPU. Range of values: 2...255 Default setting: 5 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Each incoming or outgoing frame initially runs through the MAC firewall (layer 2). If the frame is discarded at this level, it will not be checked by the IP firewall (layer 3). This means that with suitable MAC firewall rules, IP communication can be restricted or blocked. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
4. Now select the CP in the S7 station. 5. Enable the advanced firewall mode in the local security settings of the CP in the "Security > Firewall" parameter group. 6. Open the "IP rules" parameter group. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Recommendation: If your e-mail provider offers both options (STARTTLS / SSL/TLS), you should use STARTTLS with port 587. ● Port no. 465 By using SSL/TLS (SMTPS), the module sends encrypted e-mails to the SMTP server of your e-mail service provider. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
If the option is enabled, communication via SNMP is released on the device. As default, SNMPv1 is enabled. If the option is disabled, queries from SNMP clients are not replied to either via SNMPv1 or via SNMPv3. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 71
SNMP. For new roles, you can freely configure individual rights. You will find information on users, roles and the password policy in the information system of STEP 7. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
If you use communication with authentication for the module, for example SSL/TLS for secure transfer of e-mails, certificates are required. You need to import certificates of non- Siemens communications partners into the STEP 7 project and download them to the module with the configuration data: 1.
Page 73
Configuration 4.9 Security So that the CP can communicate with non-Siemens partners when the security functions are enabled, the relevant certificates of the partners must be exchanged during communication. To supply the CP with third-party certificates, follow the steps below: 1.
(HTTP, FTP etc.). The data traffic between two network components is transported practically unrestricted through another network. This allows entire networks to be connected together via a neighboring or intermediate network. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 75
● Secure connections via non-secure network structures becomes possible. Due to the combination of different security measures such as firewall, NAT/NAPT routers and VPN via IPsec tunnels, security modules protect against the following: ● Data espionage ● Data manipulation ● Unwanted access CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
2. Enter the user name, password and confirmation of the password. 3. Click the "Logon" button. You have created a new security user. The security functions are now available to you. With all further logons, log on as user. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 77
2. Enter a name for the VPN group. Configure the settings of the VPN group in the properties. These properties define the default settings of the VPN group that you can change at any time. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
4. Select the lower-level node in the tunnel list. 5. With the right mouse button, select "Delete entry" in the shortcut menu. Result: The lower-level node is now fully disabled. VPN tunnel communication can be established. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● To set up the security functions you then have the following alternative options: – Install a CP 1628 (security module) on the computer of the telecontrol server and assign the CP 1243-1 and the CP 1628 to the same security group in the configuration.
You configure the following information here: ● Address of the telecontrol server IP address or name of the telecontrol server that can be resolved by DNS. ● Port Port number of the telecontrol server CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 81
6. The available rights are displayed in the "List of rights" table. The right "Use TeleService" is displayed. 7. Enable the "Use TeleService" right for the module. 8. Following this, set the S7 protocol to "allow" in Firewall. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
You configure the data points in STEP 7 in the data point and message editor. You can find this using the project tree: Project > directory of the relevant station > Local modules > CP CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 83
Figure 4-3 Data point table You configure the remaining properties of every object using the drop-down lists of the other table columns and using the parameter boxes shown at the bottom of the screen. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 84
The sorting is indicated by an arrow in the column header. After sorting in descending order of a column the sorting can be turned off by clicking on the column header again. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 85
When you call the export function, the export dialog opens. Here, you select the module or modules of the project whose data point information needs to be exported. When necessary, you can export the data points of all modules of the project at one time. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 86
● Line 4: Parameter names (English) of the data points This line must not be changed. ● Lines 5..n: Values of the parameters according to line 4 of the individual data points You can change the parameter values for the particular station. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 87
● The telecontrol protocol used by the module differs from that of the original module. Only when importing into several modules: ● The import is aborted when a module or CPU name is different from the data in the CSV file. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Modules with the same telecontrol protocol are compatible with each other: ● TeleControl Basic All SIMATIC NET modules with the TeleControl Basic protocol: CP 1243-1, CP 1242-7 GPRS V2, CP 1243-7 LTE, CP 1542SP-1 IRC ● ST7 CP 1243-8 IRC, TIM modules capable of ST7 ●...
The following S7 data types are compatible components of ARRAY: ● Byte, USInt (total of up to 64 per data block) ● Char (total of up to 64 per data block) - CP as of firmware version 2.1.77 CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 90
Analog Input Event 32 [1] DInt Q, M, DB Analog Output Sta- 40 [1, 3] DInt Q, M, DB Analog Output 41 [1] DInt Q, M, DB Analog Output 42 [1] DInt Q, M, DB Event CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 91
On the DNP3 CP as Binary Command (12 [1]) On the master as Binary Output (10 [2]) With the data point types Binary Output Event (11) and Analog Output Event (42), you also need to enable mirroring; refer to the next section. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 92
Set point command, scaled value <49> Q, M, DB Set point command, normalised <61> Q, M, DB value with time tag CP56Time2a Set point command, scaled value <62> Q, M, DB with time tag CP56Time2a CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 93
Format of the time stamp Time stamps are transferred according to the IEC specification in the "CP56Time2a" format. Note that in the frames only the first 3 bytes for milliseconds and minutes are transferred. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Data point index with the IEC protocol The data point indexes must be unique in a CP. Data point indexes assigned twice are indicated as errors in the consistency check and prevent the project being saved. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
S7 flow before log prepro- after start address reading the cessing unreachable value overshot / undershot (always Bit status CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Less important input data points do not need to be read in every CPU scan cycle. Important input data points, on the other hand, can be prioritized for updating in every CPU scan cycle. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
The values of data points are stored in the image memory of the CP and transferred only when queried by the communications partner. Events are also stored in the frame memory (send buffer) and can be transferred unsolicited. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 98
When the connection to the communications partner returns, the CP changes back to the send buffer mode as soon as the fill level of the send buffer has fallen below 50%. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 99
Threshold value trigger (Page 101). ● Time trigger The value of the data point is transferred at configurable intervals or at a specific time of day. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
(0 → 1) of a trigger tag is evaluated that is set by the user program. When necessary, a separate trigger tag can be configured for each data point. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Note that the analog value preprocessing is performed before the check for a configured threshold value and before calculating the threshold value. This affects the value that is configured for the threshold value trigger. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 102
The method is explained based on the following example in which a threshold value of 2.0 is configured. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
In these cases, the read process value of the data point is entered in the image memory of the CP before the preprocessing cycle of the threshold value calculation (500 ms) elapses. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 104
Sequence of the analog value preprocessing options The values of analog inputs configured as an event are processed on the CPU according to the following scheme: Figure 4-5 Sequence of the analog value preprocessing CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 105
As soon as a value is acquired in the overflow or underflow range, mean value generation is stopped. The value 32767 / 7FFF or -32768 / 8000 is saved as an invalid mean value for the current mean value calculation period and sent with the next message. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 106
If the value returns to the measuring range before the fault suppression time elapses, the current value is transferred. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 107
= smoothing factor The following values can be configured for the module as the smoothing factor. ● 1 = No smoothing ● 4 = Weak smoothing ● 32 = Medium smoothing ● 64 = Strong smoothing CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 108
Entry as a decimal number according to the range of values of the assigned PLC tag from the bit memory or data area. The entry of the value 0 (zero) is interpreted as a deactivated limit value. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if limit values are configured. 4.10.11 Command outputs Parameters for command outputs With the DNP3 and IEC protocols, the following parameters can be configured for command outputs: ● LATCH_ON / LATCH_OFF ● PULSE_ON CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 110
The output is set permanently The command is rejected. to 0 (as with LATCH_OFF). * Trip-Close Code field ** Operation Type field Parameter Name: Max. number of pulses Range of val- 0 ... 255 ues: CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 111
“Max. pulse duration“ is configured. If the value is 0 (zero), no replacement value is used. If the ""Max. pulse duration" and "Pulse duration replacement time" are con- figured with zero, the command is rejected. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Activate one of the two options. ● Telecontrol server enabled Only the telecontrol server is a communications partner of the data point. ● Partner for inter-station communication Only the S7 station is a communications partner of the data point. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● Configuring the "E-mail configuration" parameter group (see "Security" parameter group) To do this, you require the following information: – Access data of the SMTP server: Address, port number, user name, password – CP's own e-mail address – Email address of the recipient CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 114
Web server of the CPU by displaying the value of the PLC tag there. For the significance of the status output in hexadecimal, refer to the section Processing status of e-mails (Page 126). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
From a PC you can access the Web server of the station via TCSB if the PC is connected to the telecontrol server via LAN. For the requirements, refer to the manual /3/ (Page 142). You will find information on the Web server in the manual /1/ (Page 141). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 116
Configuration 4.12 Access to the Web server CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Sending and receiving data via TCP or ISOonTCP ● TMAIL_C V4.0 Sending e-mails To transfer encrypted e-mails with this block, the precise time of day is required on the CP. Configure the time-of-day synchronization. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 118
For secure transfer of e-mails addressing the e-mail server using the host name You will find the description of the SDTs with their parameters in the STEP 7 information system under the relevant name. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● CPU firmware ≥ V4.2 Requirements - program blocks / STEP 7 versions Program-controlled changing of the IP parameters is supported by program blocks. The program blocks access address data stored in a suitable system data type (SDT). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 120
To be able to change the IP parameters program controlled the option "IP address is set directly at the device" must be enabled in the configuration of the IP address of the Ethernet interface of the CP. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Here, you can obtain the following static information on the selected module: ● General information on the module General information on the module ● Diagnostics status Information on the diagnostics status ● Ethernet interface Address and statistical information CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 122
The log file is created with the "Save service data" button. The data is saved in a file with the format "*.dmp" that can be evaluated by the Siemens hotline. STEP 7: The partner status The CP can signal the status of the connection to the communications partner to the CPU via a PLC tag.
VPN tunnel. Connections between a CP and telecontrol server for transferring user data are not interrupted by a TeleService-connection. The functions and the connection establishment are largely the same with the online functions and TeleService. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 124
Enter the telecontrol password to authenticate the CP with the telecontrol server The telecontrol password for the CP is configured under "CP identification" in the security settings, see also the section CP iIdentifcation with the TeleControl Basic protocol (Page 64). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
● SNMPv1 (standard) ● SNMPv3 (Security) It returns the contents of MIB objects of the standard MIB II according to RFC 1213 and the Siemens Automation MIB. ● MIB II The CP supports the following groups of MIB objects: – System –...
Diagnostics and upkeep 6.5 Processing status of e-mails ● Siemens Automation MIB The following exceptions / restrictions apply to the CP. Write access is permitted only for the following MIB objects of the system group: – sysContact – sysLocation – sysName A set sysName is sent as the host name using DHCP option 12 to the DHCP server to register with a DNS server.
Page 127
LOGIN authentication method. Try sending e-mails without authentication (no user name). 8501 Syntax error. Check the following configuration data: Alarm configuration > E-mail data (Content): Recipient address ("To" or "Cc"). • CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 128
– Recipient address ("To" or "Cc"). 8554 Transfer failed 85xx Other error message from the e-mail server Apart from the leading "8", the message corresponds to the three-digit error number of the SMTP protocol. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
New firmware versions of the CP If a new firmware version is available for the module, you will find this on the following Internet page of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/dl) Note that firmware versions as of V3 cannot be loaded on CPs with hardware product version 1.
Page 130
Web server), you can continue as described in the next section "Downloading firmware". If you terminate the connection to the Web server, the next time you can log in with the Web server without downloading the certificate using HTTP. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 131
If you close the Web server during the firmware update, you cannot change the operating status of the CPU to RUN. In this case you need to turn the CPU off and on again to change the CPU to the operating status RUN. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
CP without needing to download the project data to the station again. When the station starts up again, the new CP reads the project data from the CPU. CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Technical data Technical specifications of the CP 1243-1 Table 7- 1 Technical specifications of the CP 1243-1 Technical specifications Article number 6GK7 243-1BX30-0XE0 Attachment to Industrial Ethernet Quantity Design RJ-45 jack Properties 100BASE-TX, IEEE 802.3-2005, half duplex/full duplex, autocrossover, autonego-...
Table 7- 2 Pin assignment of the Ethernet interface View of the RJ-45 jack Signal name Assignment Transmit data + TD_N Transmit data - Receive data + Ground Ground RD_N Receive data - Ground Ground CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Division Process Industries and Drives Process Automation DE-76181 Karlsruhe Germany You will find the EC Declaration of Conformity for this product on the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/cert) > "EC Declaration of Conformity" CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 136
The product meets the requirements if you keep to the following during installation and operation: • The notes in the section Important notes on using the device (Page 31) • The installation instructions in the document /1/ (Page 141) CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 137
Class I, Zone 2, Group IIC, Temperature Class T4, Ta = 60 °C Report Number: 3049779, 3049925 Note the conditions for the safe deployment of the CP according to the section Notices on use in hazardous areas according to FM (Page 33). CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Page 138
SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications. If you require a list of the current approvals for individual devices, consult your Siemens contact or check the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/cert)
Dimension drawings Note All dimensions in the drawings of the CP are in millimeters. Figure B-1 Front view and side view left CP 1243-1 Operating Instructions, 04/2017, C79000-G8976-C365-03...
Documentation references Where to find Siemens documentation ● Article numbers You will find the article numbers for the Siemens products of relevance here in the following catalogs: – SIMATIC NET - Industrial Communication / Industrial Identification, catalog IK PI – SIMATIC - Products for Totally Integrated Automation and Micro Automation, catalog...
Page 142
Documentation references SIMATIC NET CP 1243-1 Operating Instructions Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/view/103948898) SIMATIC NET TeleControl Server Basic (Version V3) Operating Instructions Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/ps/15918/man) SIMATIC NET Industrial Ethernet Security Security basics and applications Configuration manual Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/ps/15326/man)