Siemens Synco ZW775 V2.0 Commissioning Instructions page 15

Central communication unit
Table of Contents

Advertisement

Step
Section
6
3.2
(continued)
3.2.3
3.2.4
3.2.5
7
4.1
4.1.1
4.1.2
Siemens Building Technologies
HVAC Products
Description
Edit device list
Delete devices
Needed to remove device(s) from the "List of assigned devices".
Prerequisite:
Plant > Edit device list...
Workflow:
1.
Select the device(s) from the "List of assigned devices", right-click "List of
assigned devices" to open the context menu, and select
2.
Right-click "List of assigned devices" to open the context menu and select
.
Delete devices...
3.
Click
to confirm device deletion
Yes
4.
Close the
ACS operation – [Edit device list]
5.
Select
Applications > Popcard...
no longer contains the device(s).
Refresh device list
Needed to refresh a changed KNX address or KNX serial number in the "List of
assigned devices".
• Case 1: KNX device address has changed (KNX serial number remains as is).
• Case 2: KNX serial number has changed (KNX address remains as is), i.e. a device
was replaced by a same-type device.
Prerequisite:
Plant > Edit device list...
Workflow:
1.
Select symbol
2.
Right-click to open the context menu and select
Refresh reference data points of devices
Required if devices or individual reference data points for devices were reconfigured in
the "List of assigned devices".
Prerequisite: Plant created, open applications closed.
Workflow to refresh reference data points of devices:
1.
Select
Plant > Edit device
2.
Select
Refresh reference data points
Parameterization using ACS
ACS functions
Copy standard parameter set
Workflow:
1.
Select
Applications > Parameter Setting...
2.
Right-click
Standard
to open the context menu and select
3.
Right-click
Device address 150
4.
Change the name of the parameter set
5.
The parameter set
Standard
Commissioning instructions OZW775 V2.01
Recommended commissioning
already selected.
dialog box.
to open the
[Popcard]
already selected.
in the menu tree.
list...
.
to start refreshing.
.
to open the context menu and select
Standard (1)
(1)
is ready for parameterization.
.
Insert devices...
and make sure the device list
Refresh device list
to start refresh.
Copy
.
Paste
.
(not mandatory).
CE1C5663en