Siemens SINAMICS S120 Function Manual page 861

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Unit 310-2:
● 2020 – Digital inputs, isolated (DI 0 ... DI 3, DI 22)
● 2021 – Digital inputs, isolated (DI 16 ... DI 21)
● 2030 – Digital inputs/outputs, bidirectional (DI/DO 8 ... DI/DO 9)
● 2031 – Digital inputs/outputs, bidirectional (DI/DO 10 ... DI/DO 11)
● 2032 – Digital inputs/outputs, bidirectional (DI/DO 12 ... DI/DO 13)
● 2033 – Digital inputs/outputs, bidirectional (DI/DO 14 ... DI/DO 15)
● 2038 – Digital output (DO 16)
Digital outputs
Signal processing using the digital outputs is shown in the function diagrams listed below.
Properties
● Separate power supply for the digital outputs.
● Source of output signal can be selected by parameter.
● Signal can be inverted by parameter.
● Status of output signal can be displayed
Note
Before the digital outputs can function, their own electronics power supply must be
connected.
Function diagrams (see SINAMICS S120/S150 List Manual)
Control Unit CU310-2:
● 2038 – Digital output (DO 16)
TB30:
● 9102 Isolated digital outputs (DO 0 to DO 3)
TM31:
● 9556 Digital relay outputs, isolated (DO 0 and DO 1)
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
– As a binector output
– As a connector output
Basic information about the drive system
12.5 Inputs/outputs
859