Siemens SINAMICS S120 Function Manual page 661

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

ZSW2 (status word 2)
See function diagram [2454].
Table 10- 25 Description of ZSW2 (status word 2)
Bit
Meaning
0
Drive data set DDS active, bit 0
1
Drive data set DDS active, bit 1
2
Drive data set DDS active, bit 2
3
Drive data set DDS active, bit 3
4
Drive data set DDS active, bit 4
5
Alarm class bit 0
6
Alarm class bit 1
7
Parking axis
8
Travel to fixed stop
9
Reserved
10
Pulses enabled
11
Data set changeover
12
Slave sign-of-life bit 0
13
Slave sign-of-life bit 1
14
Slave sign-of-life bit 2
15
Slave sign-of-life bit 3
ZSW1_BM (status word 1, metal industry)
See function diagram [2428].
Table 10- 26 Description of ZSW1_BM (status word 1, metal industry)
Bit
Meaning
0
Ready to start
1
Ready
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Remarks
Drive data set effective (5-bit counter)
Bits 5-6: Alarm stage of SINAMICS drives,
transferred as attribute in alarm message
value = 0: Alarm (previous alarm stage)
value = 1: Alarm class A
value = 2: Alarm class B
value = 3: Alarm class C
1
Axis parking active
0
Axis parking not active
1
Travel to fixed stop
0
No travel to fixed stop
1
Pulses enabled
0
Pulses not enabled
1
Data record changeover active
0
Data set changeover active
User data integrity (4-bit counter)
Remarks
1
Ready for switching on
Power supply on, electronics initialized, line
contactor released if necessary, pulses inhibited.
0
Not ready to start
1
Ready for operation
Voltage at Line Module (i.e. line contactor closed (if
used)), field being built up.
10.1 Communication according to PROFIdrive
Communication
Parameter
BO: r0051.0
BO: r0051.1
BO: r0051.2
BO: r0051.3
BO: r0051.4
BO: r2139.11
BO: r2139.12
BO: r0896.0
BO: r1406.8
BO:r0899.11
BO: r0835.0
Implicitly
interconnected
Parameter
BO: r0899.0
BO: r0899.1
659