Bit
Meaning
4
Reserved
5
Inhibit motor operation
Note:
During "Inhibit motoring operation", power can still be drawn from the DC link. The DC-link voltage is then no
longer controlled. The voltage level is the same as the rectified value of the current line voltage.
6
Inhibit regenerative operation
Note:
If regenerative operation is inhibited and power is fed to the DC link (e.g. by braking the motor), the DC-link
voltage increases (F30002).
7
Acknowledge fault
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
8...9
Reserved
10
Master control by PLC
Note:
This bit should not be set to "1" until PROFIdrive has returned an appropriate status via E_ZSW1.9 = "1".
11...15 Reserved
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
10.1 Communication according to PROFIdrive
Remarks
0
Disable operation
Pulse inhibit is present
-
-
1
Inhibit motor operation
Motoring operation as step-up converter is
inhibited.
0
Enable motor operation
Motoring operation as step-up converter is
enabled.
1
Inhibit regenerative operation
Regenerative operation is inhibited.
0
Enable regenerative operation
Regenerative operation is enabled.
0/1
Acknowledge fault
-
-
1
Master control by PLC
This signal must be set so that the process data
transferred via PROFIdrive is accepted and
becomes effective.
0
No master control by PLC
Process data transferred via PROFIdrive is
rejected, i.e. assumed to be zero.
-
-
Communication
Parameter
-
BI: p3532
BI: p3533
BI: p2103
-
BI: p0854
-
651