Communication
10.1 Communication according to PROFIdrive
Bit
Meaning
14
Motorized potentiometer, setpoint,
lower
Note:
If motorized potentiometer setpoint raise and lower are 0 or 1 simultaneously, the current setpoint is frozen.
15
Reserved
STW1 (control word 1), positioning mode, r0108.4 = 1
See function diagram [2475].
Table 10- 8
Description of STW1 (control word 1), positioning mode
Bit
Meaning
0
ON/OFF1
1
OFF2
Note:
Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
2
OFF3
Note:
Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
3
Enable operation
4
Reject traversing task
5
Intermediate stop
6
Activate traversing task
Note:
The interconnection p2649 = 0 is also made.
7
Acknowledge fault
638
Remarks
1
Motorized potentiometer, setpoint, lower
0
Motorized potentiometer setpoint lower not
selected
-
-
Remarks
0/1
ON
Pulse enable possible
0
OFF1
Braking with the ramp-function generator, then
pulse suppression and ready for switch on.
1
No OFF2
Enable possible
0
OFF2
Immediate pulse suppression and switching on
inhibited
1
No OFF3
Enable possible
0
Quick stop (OFF3)
Braking with OFF3 ramp p1135, then pulse
suppression and switching on inhibited.
1
Enable operation
Pulse enable possible
0
Disable operation
Cancel pulses
1
Do not reject traversing task
0
Reject traversing task
1
No intermediate stop
0
Intermediate stop
0/1
Enable setpoint
0
No effect
0/1
Acknowledge fault
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
BICO
BI: p1036
-
Parameter
BI: p0840
BI: p0844
BI: p0848
BI: p0852
BI: p2641
BI: p2640
BI: p2631,
p2650
BI: p2103
Drive functions