Table 28: Environmental Tolerances
Description
Altitude
Relative humidity
Temperature
Seismic
NOTE:
Install the MX10016 router only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.
General Site Guidelines
This topic applies to hardware components in MX10016 routers.
Tolerance
No performance degradation at sea level.
Normal operation ensured in relative humidity range of 5% through 90%,
noncondensing.
Short-term operation ensured in relative humidity range of 5% through
93%, noncondensing.
NOTE:
As defined in NEBS GR-63-CORE, Issue 3, short-term events can
be up to 96 hours in duration but not more than 15 days per year.
Normal operation ensured in temperature range of 32° F through 104° F
(0° C through 40° C).
Nonoperating storage temperature in the shipping container: –40° F
through 158° F (–40° C through 70° C).
Short-term operation ensured in temperature range of 32° F through
104° F (0° C through 40° C) at sea level.
NOTE:
As defined in NEBS GR-63-CORE, Issue 3, short-term events can
be up to 96 hours in duration but not more than 15 days per year.
Designed to comply with Zone 4 earthquake requirements per NEBS
GR-63-CORE, Issue 3.
91