Table 44: Power Specifications for the JNP10K-PWR-DC2 Power Supply
Item
DC input voltage
DC input current rating
Output power
Table 45 on page 113
shows the physical specifications for a JNP10K-PWR-DC2 power supply.
Table 45: Physical Specifications of a JNP10K-PWR-DC2 Power Supply
Specification
Height
Width
Depth
Weight

MX10016 Grounding Cable and Lug Specifications

For installations that require a separate grounding conductor to the chassis, the router must be adequately
grounded before power is connected to ensure proper operation and to meet safety and electromagnetic
Specifications
Minimum operating voltage: –40 VDC
Nominal operating voltage: –48 VDC
Operating voltage range: –40 VDC through –72 VDC
76-A maximum at minimum operating voltage (-40 VDC) with 80-A
dip switch setting and 5500-W output load.
64-A maximum at nominal operating voltage (–48 VDC) with 80-A
dip switch setting and 5500-W output load.
60-A maximum at minimum operating voltage (-40 VDC) with 60-A
dip switch setting and 4400-W output load.
50-A maximum at nominal operating voltage (-48 VDC) with 60-A
dip switch setting and 4400-W output load.
2200 W for low input (60-A) single feed
4400 W for low input (60-A) dual feed
2750 W for high input (80-A) single feed
5500 W for high input (80-A) dual feed
Value
3.5 in. (8.89 cm)
3.6 in. (9.14 cm)
16.05 in. (40.77 cm)
8.1 lb (3.67 kg)
113