10. Unscrew the nuts counterclockwise using the 13/32 in. (10 mm) nut driver or socket wrench from the
input terminal studs.
11. Remove the cable lugs from the input terminal studs.

How to Install a JNP10K-PWR-DC2 Power Supply

The JNP10K-PWR-DC2 power supply in an MX10016 chassis is a hot-removable and hot-insertable
field-replaceable unit (FRU). You can install up to 10 power supplies in an MX10016 router chassis. All
HVDC power supplies install in the rear of the chassis in the slots along the left side of the chassis.
Before you install an HVDC power supply in the chassis, ensure that you have followed all safety warnings
and cautions:
WARNING:
from the DC circuit. To ensure that all power is off, locate the circuit breaker on the panel
board that services the DC circuit, router the circuit breaker to the OFF position, and
tape the router handle of the circuit breaker in the OFF position.
WARNING:
removing a working HVDC power supply from the chassis. HVDC power supplies can
reach 158°F(70°C).
CAUTION:
a cable lug to the grounding and power cables that you supply. A cable with an incorrectly
attached lug can damage the router (for example, by causing a short circuit).
CAUTION:
You can mix DC and HVDC power supplies while swapping out one type for another
during installation.
Before performing DC power procedures, ensure that power is removed
Protect yourself from severe burns by wearing heat-protective gloves when
Before you connect power to the router, a licensed electrician must attach
Do not mix AC, DC, or HVDC power supplies in the same running chassis.
200