Performing the upgrade

Completing the CP PIV upgrade

Testing the Cores
NN43021-466
Standard 06.02
LD 137
The
commands are not applicable to CP PIV. Instead, the
CMDU/MMDU
following commands are used in LD 137.
STAT FMD
display text: Status of Fixed Media Device (FMD)
command parameter: none
STAT RMD
display text: Status of Removable Media Device(RMD)
command parameter: none
Procedure 25
Testing Core/Net 1
At this point in the upgrade, Core/Net 0 is tested from active Core/Net 1. Upon
successful completion of these tests, call processing is switched and the same
tests are performed on Core/Net 1 from active Core/Net 0. As a final step, call
processing is then switched again to Core/Net 1.
From Core/Net 1, perform these tests:
1
Perform a redundancy sanity test:
LD 135
STAT CPU
TEST CPU
2
Test the System Utility card and the cCNI cards:
LD 135
STAT SUTL
TEST SUTL
December 2013
Load program
Obtain status of CPU and memory
Test CPU
Load program
Obtain the status of the System Utility
card
Test the System Utility card