1.8.2 Setting vacation periods

During vacation periods, the controller constantly remains in reduced operation. A maximum of
10 vacation periods can be entered. Each vacation period can be separately assigned to the
heating circuits Rk1, Rk2 and/or the DHW circuit.
Parameter
Vacation period (START, STOP)
Proceed as follows:
To enter additional vacation periods, re-select – –.– – and repeat the steps 4 to 9.
16
EB 5573 EN
WE
Level / Range of values
Extended information level / 01.01 to 31.12
1.
In the extended information level (normal switch
position
) select data point for vacation periods [q].
Display:
2.
Open data point for vacation periods [ ].
Display: START
3.
If applicable, select – – – – [q].
4.
Activate editing mode for start date of vacation period
[ ].
and
blink.
5.
Edit start date of vacation period [q].
6.
Confirm start date of the vacation period.
Display: STOP, – –.– –
7.
Edit end of vacation period [q].
8.
Confirm end of vacation period [ ].
The black square at the top of the display indicate the
assignment of the vacation periods to the individual
control circuits.
9.
Select the control circuit to which the current vacation
period should apply [q].
Current vacation period applies to heating circuit 1
Current vacation period applies to heating circuit 2
Current vacation period applies to DHW circuit
The vacation period can be assigned to a single con-
trol circuit or any combination of all three circuits
(Rk1, Rk2, DHW circuit).