Start-up

2
Start-up
The modifications of the controller configuration and parameter settings described in this sec-
tion can only be performed after the valid key number has been entered.
The valid key number for initial start-up can be found on page 123. To avoid unauthorized use
of the key number, remove the page or make the key number unreadable. In addition, it is pos-
sible to enter a new, customized key number (–> section 7.15).
2.1

Setting the system code number

21 different hydraulic schematics are available. Each system configuration is represented by a
system code number. The different schematics are dealt with in section 4. Available controller
functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default set-
tings (WE). Function block parameters and parameter level settings remain unchanged.
The system code number is set in the configuration and parameter level.
Proceed as follows:
1.
Turn the rotary switch to
Display: 0 0 0 0
2.
Set valid key number [q].
3.
Confirm key number [ ].
Display: PA_
4.
Select Anl .
5.
Activate editing mode for the system code number [ ].
blinks.
6.
Edit system code number [q].
7.
Confirm system code number [ ].
Display: End
8.
Return the rotary switch to normal switch position
20
EB 5573 EN
(configuration and parameter level).
(information level).