4-Point Characteristic - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

5.1.2 4-point characteristic

t
[˚C]
VL
100
t
VLmax
90
80
70
60
50
40
30
t
20
VLmin
10
20
15
Fig. 6 · 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points for the Outdoor temperature , the Flow temperature, the Reduced flow
temperature and the Return flow temperature . The Max. flow temperature and Min. flow tempera-
ture parameters mark the upper and lower limits of the flow temperature.
Note:
The Day set point and Night set point parameters are no longer available when the 4-point
characteristic has been selected, provided no additional functions (e.g. Optimization, Flash
adaptation) have been selected.
The 4-point characteristic function can only be activated when the Adaptation function is not
active (CO1, 2 -> F08 - 0).
Functions
Adaptation
4-point characteristic
Parameters
Outdoor
Point 1
temperature
Point 2
Point 3
Point 4
P2
P3
P4
10
5
0
–5
WE
0
0
WE
–15.0 °C
–5.0 °C
5.0 °C
15.0 °C
P1 to P4
t
VL
t
A
P1
---min
---max
t
A
–10
–15 –20
[˚C]
Configuration
CO1, 2 -> F08 - 0
CO1, 2 -> F11 - 1
Parameter level / Range of values
PA1, 2 / –40.0 to 50.0 °C
Functions of the heating circuit
Points 1 to 4
Flow temperature
Outdoor temperature
Min. t
VL
Max. t
VL
4-point characteristic
Reduced 4-point characteristic
EB 5573 EN
49

Hide quick links:

Advertisement

Table of Contents
loading