Functions
Storage tank sensor SF1
Thermal disinfection
WE
Configuration
1
CO4 -> F01 - 1
0
CO4 -> F14 - 1
3
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = daily, 1 = Monday, ..., 7 = Sunday
00:00
Start time / 00:00 to 23:45h; in steps of 15 minutes
04:00
Stop time / 00:00 to 23:45h; in steps of 15 minutes
70.0 °C
Disinfection temperature / 60.0 to 90.0 °C
10.0 °C
Set point boost / 0 to 50 °C
0 min
Hold time of disinfection time / 0 to 255 min
bE=1
bE=1, bE=0 (start of disinfection with terminal 03/12 =
ON, OFF; only applies when Start time = Stop time)
Functions of the DHW circuit
EB 5573 EN
69