Parameters in PA4 level: DHW heating
Parameters
Min. DHW temperature
Max. DHW temperature
Hysteresis
Charging temperature boost
Max. charging temperature
Lag of storage tank charging pump
Max. return flow temperature
Solar pump ON
Solar pump OFF
Max. storage tank temperature
Function block parameters
F03 - 1: KP (limiting factor)
F06 - 1: Stop parallel operation in case of deviation
F06 - 1: Flow limit temp. for parallel pump operation
F08 - 1: Activate priority in case of deviation
F08 - 1: KP (Einflussfaktor)
F09 - 1: Activate priority in case of deviation
F12 - 1: KP (proportional gain)
F12 - 1: Tn (reset time)
F12 - 1: TV (derivative-action time)
F12 - 1: TY (valve transit time)
F12 - 0: Hysteresis
F12 - 0: Min. ON time
F12 - 0: Min. OFF time
F13 - 1: Max. deviation
F14 - 1: Day of the week
F14 - 1: Start time
F14 - 1: Stop time
F14 - 1: Disinfection temperature set point
F14 - 1: Set point boost
F14 - 1: Hold time of disinfection temperature
PA4
Range of values
5.0 to 90.0 °C
5.0 to 90.0 °C
1.0 to 30.0 °C
0.0 to 50.0 °C
20.0 to 130.0 °C
0.0 to 10.0
0.0 to 90.0 °C
1.0 to 30.0 °C
0.0 to 30.0 °C
20.0 to 90.0 °C
CO4
Range of values
0.1 to 10.0
0 to 10 min
20.0 to 90.0 °C
2 to 10 min
0.1 to 10.0
2 to 10 min
0.1 to 50.0
1 to 999 s
0 s; Do not change!
5 to 240 s
1.0 to 30.0 °C
0 to 10 min
0 to 10 min
2.0 to 10.0 °C
1–7, 1 to 7
00:00 to 23:45h
00:00 to 23:45h
60.0 to 90.0 °C
0.0 to 50.0 °C
0 to 255 min
Appendix
117
EB 5573 EN

Hide quick links: