Functions of the heating circuit
Note:
Direct sunshine can cause the room temperature to increase and thus result in the premature de-
activation of the heating system.
When the room temperature decreases while the heating system is shortly outside its
times-of-use, this can prematurely cause the controller to heat up to the Day set point.
Functions
Room sensors RF1/2
Outdoor sensor AF1
Optimization
Parameters
Day set point
Night set point
5.8

Flash adaptation

To ensure that the controller reacts immediately to room temperature deviations during rated or
reduced operation, the function block setting CO1, 2 -> F09 - 1 needs to be made.
The heating is then always switched off as soon as the room temperature exceeds the Day set
point or Night set point by 2 °C.
Heating first starts again when the room has cooled off and the room temperature is 1 °C above
the Set point . The flow temperature set point is corrected if the Cycle time and Gain K
a value other than 0. The Cycle time determines the intervals at which the flow temperature set
point is corrected by 1 °C. A Gain K
crease in flow temperature set point when a sudden deviation in room temperature arises. A
Gain K
setting of 10.0 is recommended.
p
Note:
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated after the cooling load has been eliminated!
56
EB 5573 EN
WE
Configuration
0
CO1, 2 -> F01 - 1
1
CO1 -> F02 - 1
0
CO1, 2 -> F07 - 1
WE
Switch position / Range of values
20.0 °C
/ 0.0 to 40.0 °C
15.0 °C
/ 0.0 to 40.0 °C
set to a value other than 0 causes a direct increase/de-
P
are set to
P