Functions Of The Heating Circuit; Weather-Compensated Control - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Functions of the heating circuit

5
Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
5.1

Weather-compensated control

When weather-compensated control is used, the flow temperature is controlled according to the
outdoor temperature. The heating characteristic in the controller defines the flow temperature
set point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature required
for weather-compensated control can either be measured by an outdoor sensor or it can be re-
ceived over an 0 to 10 V input.
˚
t
[
C]
VL
130
120
110
100
90
80
70
60
50
40
30
20
20
16
12
Fig. 5 · Gradient characteristics
Function
Outdoor sensor AF1
Outdoor temperature received
over 0 to 10 V input
46
EB 5573 EN
3.2
8
4
0
-4
-8
-12
WE
1
0
–20 °C
50 °C
2.9
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
t
A
˚
-16
-20
[
C]
Configuration
CO1 -> F02 - 1
CO5 -> F23 - 1
Lower transmission range / –30 to 100 °C
Upper transmission range / –30 to 100 °C
t
Flow temperature
VL
t
Outdoor temperature
A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents