Entering day and night set points

The desired room temperature for the day ( Day set point ) and a reduced room temperature for
the night ( Night set point ) can be entered in the controller for the heating circuits.
In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
Switch position
Parameters
Day set point
DHW temperature set point
Switch position
Parameters
Night set point
DHW sustained temperature
Proceed as follows:
1.
Turn the rotary switch to the required data point:
for Day set point or DHW temperature set point
for Night set point or DHW sustained temperature
blinks.
4
In systems Anl 1.0, 1.9 and 3.5, the current set point is directly indicated. Skip the
following steps 2 and 3 (selecting the control circuit).
2.
Select the control circuit for which the set point is to be entered [q]:
Heating circuit 1
Heating circuit 2
DHW circuit
4
Only those control circuits are available for selection which can be controlled by the
system (Anl) selected.
3.
Confirm the control circuit [ ].
Display: current set point
4.
Adjust set point [q].
5.
Return the rotary switch to normal switch position
18
EB 5573 EN
WE
Rk1, Rk2
20 °C
55 °C
WE
Rk1, Rk2
20 °C
40 °C
Range of values
0 to 40 °C
Min. to max. DHW temperature
Range of values
0 to 40 °C
Min. to max. DHW temperature
(information level).