Parameter Lists - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

12.2

Parameter lists

PA1: Parameters Rk1 (heating circuit 1)
PA2: Parameters Rk2 (heating circuit 2)
Display
Parameter designation
Range of values (default)
Gradient, flow
0.2 to 3.2 (1.8)
(with CO1, 2 -> F05 - 1: 0.2 to 1.0 (1.0) applies)
Level (parallel shift)
–30.0 to 30.0 °C (0.0 °C)
Min. flow temperature
5.0 to 130.0 °C (20.0 °C)
Max. flow temperature
5.0 to 130.0 °C (90.0 °C)
(with CO1, 2, 3 -> F05 - 1: 5.0 to 50.0 °C (50.0 °C) applies)
Appendix
103
EB 5573 EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents