Manual mode

3
Manual mode
Switch to manual mode to configure all outputs, refer to wiring diagram (-> section 11).
NOTICE
The frost protection does not function when the controller is in manual mode.
Proceed as follows:
1.
Turn the rotary switch to
2.
Select output depending on the control circuit (q):
POS_
Positioning value in percent
UP_
Activation/deactivation of the circulation pump (heating)
SLP
Activation/deactivation of the storage tank charging pump
TLP
Activation/deactivation of the heat exchanger charging pump
CP
Activation/deactivation of the solar circuit pump
ZP
Activation/deactivation of the circulation pump (DHW)
3.
Confirm the output [ ].
The display blinks.
4.
Change positioning value/switching state [q].
5.
Confirm setting [ ].
The modified values remain active as long as the controller is in manual mode.
6.
Return the rotary switch to normal switch position
The manual mode is deactivated.
Note: The outputs of the controller are not affected by simply turning the rotary switch to
(manual level). You have to actually enter a positioning value or activate/deactivate the pumps
to configure the outputs.