5.1.1 Gradient characteristic

Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem-
perature to increase in order to keep the room temperature constant.
By varying the parameters Gradient and Level , you can adapt the characteristic to your individ-
ual requirements:
[°C]
t
VL
20
0
[°C]
t
VL
20
0
[°C]
t
VL
20
0
[°C]
t
VL
20
0
The gradient needs to be increased if the room temperature
drops when it is cold outside.
t
A
–20
[°C]
The gradient needs to be decreased if the room temperature
rises when it is cold outside.
t
A
–20
[°C]
The level needs to be increased and the gradient decreased if
the room temperature drops when it is mild outside.
t
A
–20
[°C]
The level needs to be decreased and the gradient increased if
the room temperature rises when it is mild outside.
t
A
–20
[°C]
Functions of the heating circuit