F Function
11 Reserved
12 Creep feed rate
limitation
13 Reserved
14 UP1 operation to
cover own demand
15 Release controller
at BE1
16 Return flow
temperature
limitation with P
algorithm
17 Reserved
18 Reserved
19 Temperature
monitoring
20 Sensor calibration
21 Locking manual
level
22 Locking the rotary
switch
23 Outdoor
temperature
received over 0 to
10 V input
F Function block number, WE Default value, Anl System code number
Comment
WE
Anl
Function block parameters / Range of values (default)
0
Not Anl
CO5 -> F12 - 1: Creep feed rate limitation,
1.9
Input over terminals 04/12
Function block parameter:
bE=1, bE=0 (bE=1)
0
Anl 3.0
CO5 -> F14 - 1: Feeder pump UP1 also starts to cover
demand of control circuit Rk2.
0
All
CO5 -> F15 - 1: FG1 has no function
Select bE= 1, bE=0 (bE=1)
0
All
CO5 -> F16 - 1: Return flow temperature limitation with
P-action only
0
All
CO5 -> F19 - 1: Temperature monitoring active
1
All
CO5 -> F20 - 1: Adjusting all sensor calibration values
CO5 -> F20 - 0: Deleting all adjusted sensor calibration
values
0
All
CO5 -> F21 - 1: In switch position
applies
0
All
CO5 -> F22 - 1: Rotary switch without function – Access
after entering key number still possible.
0
All
CO5 -> F23 - 1: Outdoor temperature received over 0 to
10 V input
Function block parameters:
Lower transmission range / –30 to 100 °C (–20 °C)
Upper transmission range / –30 to 100 °C (50 °C)
*Not in systems Anl 1.0, 1.5, 1.6, 3.0, 3.5, 4.0, 11.x
Appendix
, automatic mode
101