Samson TROVIS 5573 Mounting And Operating Instructions page 95

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

CO2: Rk2 · Heating circuit 2 (systems Anl 3.x, 4.x and 10.0)*
F Function
01 Room sensor RF2
02 Reserved
03 Return flow sensor
RüF2
04 Reserved
05 Underfloor heating
Drying of jointless
floors
06 Reserved
07 Optimization
08 Adaptation
09 Flash adaptation
10 Reserved
11 4-point
characteristic
Comment
Function block parameters / Range of values (default)
WE
Anl
0
All*
CO2 -> F01 - 1: Temperature display and input FG2 for
Type 5244/5257-5 Room Panel active
TROVIS 5570 Room Panel:
CO2 -> F01 - 1 and CO7 -> F04 - 1
1
10.x
CO2 -> F03 - 1: Sensor and limiting function active
Function block parameter:
0
3.0, 4.x
KP (limiting factor) / 0.1 to 10.0 (1.0)
0
All*
CO2 -> F05 - 1: Limitation of the adjustment ranges
Function block parameters:
Start temperature / 20 to 60 °C (25 °C)
Temperature rise per day / 1.0 to 10.0 °C (5.0 °C)
Maximum temperature / 25.0 to 60.0 °C (45.0 °C)
Maintaining time of max. temp. / 0 to 10 days (4 days)
Temperature reduction per day / 0.0 to 10.0 °C (0.0 °C)
SToP,
0
All*
CO2 -> F07 - 1: Only with
0
All*
CO2 -> F08 - 1: Only with
0
All*
CO2 -> F09 - 1: Only with CO2 -> F01 - 1
Function block parameters:
Cycle time / 0 or 1 to 100 min (20 min)
KP (gain) / 0.0 to 25.0 (0.0)
0
All*
CO2 -> F11 - 1: 4-point characteristic, only with
CO2 -> F08 - 0
CO2 -> F11 - 0: Gradient characteristic
n
nn
nnn
STArT,
STArT,
Appendix
STArT
• CO2 -> F01 - 1
• CO1 -> F02 - 1
• CO2 -> F01 - 1
• CO1 -> F02 - 1
• CO2 -> F11 - 0
EB 5573 EN