Adaptation - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Functions of the heating circuit
5.9

Adaptation

The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (CO1, 2 -> F11 - 0). The refer-
ence room, where the room sensor is located, represents the entire building and is monitored to
ensure that the room set point ( Day set point) is maintained. When the mean measured room
temperature in rated operation deviates from the adjusted set point, the heating characteristic is
modified accordingly for the following time-of-use. The corrected value is displayed in PA1, 2
parameter levels under Gradient, flow .
Functions
Room sensors RF1/2
Outdoor sensors AF1/2
Adaptation
4-point characteristic
Parameters
Day set point
Night set point
Note: If the Flash adaptation function is already configured with a small cycle time, the Adap-
tation function should not be configured as well.
58
EB 5573 EN
WE
Configuration
0
CO1, 2 -> F01 - 1
1
CO1, 2 -> F02 - 1
0
CO1, 2 -> F08 - 1
0
CO1, 2 -> F11 - 0
WE
Switch position / Range of values
20.0 °C
/ 0.0 to 40.0 °C
15.0 °C
/ 0.0 to 40.0 °C