Samson TROVIS 5573 Mounting And Operating Instructions page 102

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Appendix
CO6: Modbus (all systems)
F Function
01 Modbus
02 Modbus 16-bit
addressing
03 Modem function
04 Automatic
modem
configuration
05 Lock dial-up
06 Dial-up also
upon corrected
error
07 Control system
monitoring
08 Text message
F Function block number, WE Default value, Anl System code number
102
EB 5573 EN
Comment
WE
Anl
Function block parameters / Range of values (default)
1
All
CO6 -> F01 - 1: Modbus active
0
All
CO6 -> F02 - 1: 16-bit addressing, only with CO6 -> F01 - 1
CO6 -> F02 - 0: 8-bit addressing
0
All
CO6 -> F03 - 1 Only with
0
All
CO6 -> F04 - 1 Only with
0
All
CO6 -> F05 - 1: No dial-up to GLT in case of error,
only with CO6 -> F03 - 1
0
All
CO6 -> F06 - 1: Dial-up to GLT also to indicate that an error
has been corrected, only with CO6 -> F03 - 1
0
All
CO6 -> F07 - 1: Resetting all level bits to "autonomous" when
there is no communication, only with CO6 -> F01 - 1
0
All
CO6 -> F08 - 1: Sending of text message active
• CO6 -> F01 - 1
• CO6 -> F08 - 1
• CO6 -> F03 - 1
• CO6 -> F08 - 1