Appendix
Display
104
EB 5573 EN
Parameter designation
Range of values (default)
4-point characteristic
Press rotary pushbutton ( ) to set the following parameters:
outdoor temperature,
flow temperature,
reduced flow temperature and
return flow temperature
4-point characteristic
Point 1: Outdoor temperature
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
–30.0 to 50.0 °C
(point 1: –15.0 °C, point 2: –5.0 °C, point 3: 5.0 °C,
point 4: 15.0 °C)
4-point characteristic
Point 1: Flow temperature
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
5.0 to 130.0 °C
(point 1: 70.0 °C, point 2: 55.0 °C, point 3: 40.0 °C,
point 4: 25.0 °C)
4-point characteristic
Point 1: Reduced flow temperature
Reduced flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
5.0 to 130.0 °C
(point 1: 60.0 °C, point 2: 40.0 °C, point 3: 20.0 °C,
point 4: 20.0 °C)
4-point characteristic
Point 1: Return flow temperature
Return flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
5.0 to 90.0 °C
(points 1 to 4: 65.0 °C)