Flash Adaptation Without Outdoor Sensor (Room Temperature Dependent) - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Functions
Room sensors RF1/2
Flash adaptation
Parameters
Day set point
Night set point
5.8.1 Flash adaptation without outdoor sensor (room temperature
dependent)
The flow temperature control starts with Day set point for flow in rated operation or with Night
set point for flow in reduced operation as no set points calculated using characteristics exist
without an outdoor sensor. The Cycle time determines the intervals at which the flow tempera-
ture set point is corrected by 1 °C. The heating is then always switched off as soon as the room
temperature exceeds the Day set point or Night set point by 2 °C. Heating first starts again
when the room has cooled off and the room temperature is 1 °C above the Set point . A Gain K
set to a value other than 0 causes a direct increase/decrease in flow temperature set point when
a sudden deviation in room temperature arises. A Gain K
Functions
Room sensors RF1/2
Outdoor sensors AF 1/2
Flash adaptation
Parameters
Day set point
Night set point
Parameters
Day set point for flow
Night set point for flow
WE
Configuration
0
CO1, 2 -> F01 - 1
0
CO1, 2 -> F09 - 1
20 min
Cycle time / 0 to 100 min
0.0
KP (gain) / 0.0 to 25.0
WE
Switch position / Range of values
20.0 °C
/ 0.0 to 40.0 °C
15.0 °C
/ 0.0 to 40.0 °C
WE
Configuration
0
CO1, 2 -> F01 - 1
1
CO1, 2 -> F02 - 0
0
CO1, 2 -> F09 - 1
20 min
Cycle time / 1 to 100 min
0.0
KP (gain) / 0.0 to 25.0
WE
Switch position / Range of values
20.0 °C
/ 0.0 to 40.0 °C
15.0 °C
/ 0.0 to 40.0 °C
WE
Parameter level / Range of values
50.0 °C
PA1, 2 / 5.0 to 130.0 °C
30.0 °C
PA1, 2 / 5.0 to 130.0 °C
Functions of the heating circuit
setting of 10.0 is recommended.
P
P
57
EB 5573 EN