Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the
back panel of the housing.
Connecting the actuators
4
0 to 10 V control output:
Use cables with a minimum cross-section of 2 x 0.5 mm².
4
Three-step or on/off outputs:
Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the con-
troller output. The direction of travel needs to be checked at start-up.
Connecting the pumps
Connect all cables with at least 1.5 mm² to the terminals of the controller as illustrated in the wiring
diagram.
CAUTION!
The electric actuators are not automatically supplied with a voltage by the controller. They can
be connected over terminals 25 and 28 to an external voltage source.
If this is not the case, connect a jumper from terminal 18 to terminals 25 and 28.
Legend for wiring diagram:
AF
Outdoor sensor
BE
Binary input
FG
Potentiometer
RF
Room sensor
RüF Return flow sensor
SF
Storage tank sensor
VF
Flow sensor
CP
Solar circuit pump
Rk
Control circuit
UP
Circulation pump
SLP
Storage tank charging pump
TLP
Heat exchanger charging pump
ZP
Circulation pump (DHW)
Electrical connection
91
EB 5573 EN