Appendix
PA6: Modbus parameters
Parameter designation
Display
Range of values (default)
Station address (ST)
1 to 247 (255)
(with CO6 -> F02 - 1: 1 to 32000 applies)
Modem dialing pause (P)
0 to 255 min (5 min)
Modem time-out (T)
1 to 255 min (5 min)
Number of redialing attempts to building control station (C)
1 to 255 (15)