1.8.2 Setting vacation periods

During vacation periods, the controller constantly remains in reduced operating mode. A
maximum of 10 vacation periods can be entered. Each vacation period can be assigned
separately to the heating circuits Rk1 to Rk2 and/or to the DHW circuit.
Parameter
Vacation period (START, STOP)
Proceed as follows:
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
To enter additional vacation periods, re-select – – – – and repeat the steps in the fields
highlighted in gray.
18
EB 5575 EN
WE
Level / Range of values
Extended operating level / 01.01 to 31.12
q
In extended operating level, select "Vacation periods".
Display shows:
Open data point "Vacation periods".
Display shows: START , – –.– – (day.month)
q
If applicable, select – – – – .
Activate editing mode for start date of vacation period.
blinks.
q
Edit start date of vacation period.
Confirm start date of vacation period.
q
Edit end of vacation period.
Display shows: STOP, – –.– – (day.month)
Confirm end date of the vacation period.
Black squares under 1 to 4 at the top of the display
indicate the assignment of the vacation periods to the
individual heating circuits.
q
Select the control circuit to which the current vacation
period should apply.
Current vacation period applies to circuit Rk1
Current vacation period applies to circuit Rk2
Current vacation period applies to DHW circuit
The vacation period can be assigned to a single control
circuit or any combination of all three control circuits
(Rk1 to Rk2, DHW circuit).