Operation
1.8.2 Setting vacation periods
During vacation periods, the controller constantly remains in reduced operating mode. A
maximum of 10 vacation periods can be entered. Each vacation period can be assigned
separately to the heating circuits Rk1 to Rk2 and/or to the DHW circuit.
Parameter
Vacation period (START, STOP)
Proceed as follows:
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
To enter additional vacation periods, re-select – – – – and repeat the steps in the fields
highlighted in gray.
18
EB 5575 EN
WE
Level / Range of values
–
Extended operating level / 01.01 to 31.12
q
In extended operating level, select "Vacation periods".
Display shows:
Open data point "Vacation periods".
Display shows: START , – –.– – (day.month)
q
If applicable, select – – – – .
Activate editing mode for start date of vacation period.
blinks.
q
Edit start date of vacation period.
Confirm start date of vacation period.
q
Edit end of vacation period.
Display shows: STOP, – –.– – (day.month)
Confirm end date of the vacation period.
Black squares under 1 to 4 at the top of the display
indicate the assignment of the vacation periods to the
individual heating circuits.
q
Select the control circuit to which the current vacation
period should apply.
Current vacation period applies to circuit Rk1
Current vacation period applies to circuit Rk2
–
Current vacation period applies to DHW circuit
The vacation period can be assigned to a single control
circuit or any combination of all three control circuits
(Rk1 to Rk2, DHW circuit).