Memory Module; Data Logging - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Communication
9.4

Memory module

The use of a memory module (order no. 1400-9379) is particularly useful to transfer all data
from one TROVIS 5573 Controller to several other TROVIS 5573 Controllers.
The memory module is plugged into the RJ-45 jack at the side. Once the module has been con-
nected, "73 SP" is displayed. If the memory module already contains data from a different
TROVIS 5573 Controller, turn the rotary pushbutton until "SP 73" is displayed.
4
Pressing the rotary pushbutton to confirm "73 SP" causes the controller settings to be trans-
ferred to the memory module.
4
Pressing the rotary pushbutton to confirm "SP 73" causes the saved controller settings to be
transferred from the memory module to the controller.
During the data transfer, the bars on the display indicate the progress. When the transfer was
successful, "I.O." is displayed. After that, the connection between controller and memory mod-
ule can be terminated.
Using TROVIS-VIEW (order no. 6661-1014), it is possible to configure all controller settings in
a convenient user interface on the PC and to document these settings.
9.5

Data logging

A data logging module (order no. 1400-9378) saves the following controller data every two
minutes:
4
Temperatures measured by the sensors
4
Control signals [%]
4
Switching states of the pump outputs
4
Error status register and its archive data
4
Access to the controller settings
The data logging module is connected to the RJ-45 jack at the side of the controller.
The controller starts to write over the oldest data as soon the memory of the data logging mod-
ule is full after approximately eight days. The current memory capacity of the data logging
module can be read in the extended information level under Info 2 as the second in the se-
quence (range of values: 0 to 6035). Directly after inserting the data logging module, data can
be first read after the first scanning cycle has been performed.
The Datalogging Viewer software allows the data to be viewed in graph format. The USB
converter 3 (order no. 1400-9377) is required to connect the data logging module to a com-
puter. The Datalogging Viewer software is supplied with the USB converter 3.
86
EB 5573 EN