Samson TROVIS 5573 Mounting And Operating Instructions page 106

Automation system trovis 5500 heating and district heating controller
Hide thumbs Also See for TROVIS 5573:
Table of Contents

Advertisement

Appendix
Parameter designation
Display
Range of values (default)
Return flow temperature foot
5.0 to 90.0 °C (65.0 °C)
Max. return flow temperature
5.0 to 90.0 °C (65.0 °C)
Set point boost of primary exchanger control
0.0 to 50.0 °C (5.0 °C)
Only in PA1 parameter level
Set point for binary demand processing
5.0 to 130.0 °C (40.0 °C)
Only in PA1 parameter level
Day set point for flow temperature
5.0 to 130.0 °C (50.0 °C)
Only for flash adaptation without outdoor sensor