Figure 5-2 Screwing Cabinets Together - Siemens SINAMICS GM150 Operating And Installation Instructions

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

Preparation
Ensure that access to the holes in the bottom of the cabinets is unobstructed. Remove the
guard covers.
To screw the transport units together, you will need the following mounting hardware:
● Hexagon nuts ISO 4032-M8-8 A2L
● Contact washers SN70093-8-FSt-mechZn-f
● Threaded pin M8 x 15.5
Screw cabinets together
To screw the cabinets together, proceed as follows:
1. Align the cabinets.
2. Insert the threaded pins through the holes
3. Attach the contact washers to the threaded pins.
4. Screw the cabinets together using the nuts with a torque of 32 Nm.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Figure 5-2
Screwing cabinets together
5.4 Screwing the transport units together
. Use the corner holes and then every 300 mm.