Connecting The Encoder To The Smc30 Sensor Module - Siemens SINAMICS GM150 Operating And Installation Instructions

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

Connect the cables in accordance with the following table:
Terminal
X950 : 1
X950 : 2
X950 : 3
X950 : 4
X950 : 5
X950 : 6
X950 : 7
X950 : 8
Note
For more information about terminal assignments, see the circuit manual of the drive.
Note
You can find a list and description of the feedback signals of the circuit-breaker in the
commissioning manual of the drive.
6.5.8

Connecting the encoder to the SMC30 Sensor Module

Safety instructions
NOTICE
Incorrectly connected external encoder
If the external encoder is not connected or operated correctly, this can damage the
components.
Only one measuring system can be connected to each sensor module.
The sensor module is wired internally to the customer terminal strip. For further information,
see the circuit manual.
Note
Observe the five safety rules when performing any work.
Procedure
1. Allow unimpeded access to the SMC30 Sensor Module.
2. Disconnect the cabinet from the power supply.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Cable
Cable 1
Redundant cable 2
Cable 3
Circuit-breaker
L + from circuit-breaker
OFF switching command to circuit-breaker
L – from circuit-breaker
L + redundant from circuit-breaker
OFF switching command redundant to circuit-breaker
L – redundant from circuit-breaker
ON supply cable from circuit-breaker
ON switching command to circuit-breaker
Electrical connection
6.5 Connection
113