B.2.4.6

Analog and digital outputs

Table B-20
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Max. connectable cross-section 1.5 mm²; type: Screw terminal
B.2.4.7

Switch for the analog inputs

Table B-21
Switch
S5.0
S5.1
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Power Stack Adapter 2: Analog and digital outputs
Designation
Technical specifications
X231
X232
M
Max. output voltage:
DO 3
DO 7
Supply voltage at X210.3 minus approximately 2 V
Max. load current per output:
DO 2
DO 6
300 mA, continuously short-circuit-proof
M
Output delay:
M
● For "0" to "1": Typ. 100 μs at 0.3 A resistive load
DO 1
DO 5
● For "1" to "0": Typ. 10 μs at 0.3 A resistive load
DO 0
DO 4
M
AO 3-
AO 7-
Voltage range:
0 V to 10 V, short-circuit proof
AO 3+
AO 7+
Max. load current per output: 3 mA
AO 2+
AO 6+
Resolution: 12 bits
AO 2-
AO 6-
AO 1-
AO 5-
AO 1+
AO 5+
AO 0+
AO 4+
AO 0-
AO 4-
Power Stack Adapter 2: Switch for the analog inputs
Function
Switchover, analog input AI0:
Voltage (V)/Current (I)
Switchover, analog input AI1:
Voltage (V)/Current (I)
Technical data and drawings
B.2 Terminal assignments
Technical specifications
Current range 0 mA to 20 mA, can be additionally
reduced to 4 mA to 20 mA via software (wire-break
monitoring);
Voltage range 0 V ... 10 V