Signal Processing; Table 3-8 Connector -X36 - Siemens SINAMICS GM150 Operating And Installation Instructions

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

Description
3.5 Description of the components
Pin
3
4
5
6
The external supply voltage 2P24 is connected at connector –X35. This voltage, supplied from a 10 A power supply unit, is
selectively distributed via several single-pole miniature circuit-breakers. Their auxiliary contacts can be wired to HK_1 and
HK_2. In addition, a further external power supply 2P24_2 can be monitored for undervoltage.
Table 3-8
Connector -X36
Pin
1
2
Connector –X36 informs the closed-loop control system of the monitoring state.
3.5.11.4

Signal processing

Tasks of the operational amplifier
The Power Stack Adapter returns analog signals within a range of values from 0 V to 10 V to
the DM10 diagnosis module. Because of this fixed value range, signed signals such as the
actual speed value cannot be represented. Eight AD8674 operational amplifiers boost the
voltage signal (reduced by 5 V) by a factor of 2. As a result of this signal handling, it is also
possible to represent signals in a range of values from -10 V to +10 V.
In order to be able to perform signal handling with great accuracy, the operational amplifiers
must satisfy the following criteria:
● Low noise: 2.8 nV/√Hz
● Large bandwidth: 10 MHz
● Low quiescent input curent: max. 12 nA
● Low offset voltage: max. 75 μV
The signals are relayed to the following interfaces:
● For diagnosis to the process data acquisition system (option G66).
● For alternative diagnosis with the aid of indicating instruments (option K21/K22).
● Via additional isolation amplifiers to the control station / I&C.
● For simplified diagnosis with an oscilloscope to measuring sockets X20 to X27.
50
Signal type
Signal designation
2M24
Ground
2M24
Ground
HK_1
Auxiliary contact: A1
HK_2
Auxiliary contact: A2
Signal type
PS_OK
2M24
Signal designation
Power Supply OK
Ground
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents