Installation

5.8 Connecting the interface terminals

3. Screw the connection jumper firmly in place using the supplied M5 nuts with a torque of 3
4. Mount the connection jumpers on the bottom of the DC bus in exactly the same way.
5.8
Connecting the interface terminals
Connecting the interface terminals of several cabinets
If several cabinets are set up as one unit, the interface terminals of the cabinets must be
connected with each other.
92
Nm.
Connection jumper
Copper spacer plate
Figure 5-4
DC-bus connection
Note
In exceptional cases the connection jumpers are not shipped in the assembled state.
Assemble them as shown in the diagram "Assembling the DC bus connection".
Insulating plate
Busbar
Rivets (not supplied)
Figure 5-5
Assembling the DC-bus connection
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017