6.5.4

Connect the power cable to the motor and the supply system

When connecting the cables, observe all the conditions regarding conductor protection. Do
not exceed the permitted cable lengths between the converter output and motor. The distance
between the motor cable and the signal cable should be at least 20 cm. Do not lay grid-side
and motor supply cables in parallel to each other.
The positions of the connections are shown in the layout diagrams. Detailed wiring notes for
the converter are contained in the circuit manual of the converter.
Select the appropriate cable depending on the following conditions:
● Routing conditions
● Accumulation of cables
● Ambient temperature
● Bending radii
● Output voltage
Observe the connection capabilities on the converter and on the motor terminal box.
Procedure
1. Open the cabinet.
2. Remove or slide away the cover plate for the motor cable penetration.
Note
To route the power cables from above into the cabinet, remove the cover plate at the top of
the cabinet.
NOTICE
Danger of thermal damage
Inadequately fastened cables at the connection point represent a high electrical transfer
resistance that can cause thermal damage (contact erosion) during operation.
Tighten the screws with the specified torque.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Electrical connection
6.5 Connection
109