Table B-11
Terminal assignment of customer interface TM31
Terminal module
Connec‐
tor
.HC-A31
-X521
B.2.2

Terminal assignment of the NAMUR terminal strip (option B00)

The NAMUR terminal strip is a standard terminal strip defined for the chemicals/
pharmaceutical industry. It is defined as follows:
Table B-12
Terminal assignment of NAMUR terminal strip
Terminal
No.
-A1-X2
1
1.0
1.1
3
3.0
3.1
10
11
12
13
14
15
16
17, 18
30, 31
32, 33
34
35
36
50, 51
AI 0/4 mA to 20 mA
60, 61
AO 0/4 mA to
62, 63
AO 0/4 mA to
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Terminal
1,2
AI
3,4
AI
1,2
AO
4,5
AO
Designation
M
Reference conductor to 24 VDC
P24
DI
ON command drive
DI
DI
DI
DI
DI
DI
Power disconnection
Ready for operation
Operation; motor turning
DO (COM)
DO (NO)
DO (NC)
Main actual speed value
20 mA
20 mA
p4052.0
p1070
p4052.1
p1075
p4071.0
r0063
p4071.1
Preassignment
supply
24 VDC supply
OFF (dynamic)
Faster
Slower
RESET
Lock
Counterclockwise
Fault
Speed setpoint
Motor current
Technical data and drawings
B.2 Terminal assignments
Internal control
Main speed setpoint
Supplementary speed setpoint
Actual speed value
Supplementary actual speed value
Comments
3 terminals
Protected internally with fuse (2 A)
3 terminals
See .HC -A31 -X520:3.
≙ MOP raise
≙ MOP lower
≙ Acknowledge faults
≙ OFF3
"0" signal for CW phase sequence
"1" signal for CCW phase sequence
≙ direction of rotation changeover
External safety circuit
Circuit-breaker no OFF command
Relay output (NO contact)
Relay output (NO contact)
Relay output (two-way contact)
Defaulted with motor current – can be repara‐
meterized for other variables.