Preparation
Ensure that access to the holes in the bottom of the cabinets is unobstructed. Remove the
guard covers.
To screw the transport units together, you will need the following mounting hardware:
● Hexagon nuts ISO 4032-M8-8 A2L
● Contact washers SN70093-8-FSt-mechZn-f
● Threaded pin M8 x 15.5
Screw cabinets together
To screw the cabinets together, proceed as follows:
1. Align the cabinets.
2. Insert the threaded pins through the holes
3. Attach the contact washers to the threaded pins.
4. Screw the cabinets together using the nuts with a torque of 32 Nm.
5.5

Connecting to the foundation

Preparatory steps
1. Ensure that access to the holes in the bottom of the cabinets is unobstructed.
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE
Figure 5-2
Screwing cabinets together
5.5 Connecting to the foundation
. Use the corner holes and then every 300 mm.