Screwing The Transport Units Together - Siemens SINAMICS GL150 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Screw type
M5
M6
M8
M10
M12
M16
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VDE 609-1
5.4

Screwing the transport units together

NOTICE
Material damage caused by mechanical pressure on components
Stress that occurs during transport may exert mechanical pressure on the components.
Material damage can result.
● Line the cabinets up precisely with each other in order to avoid shearing forces when the
● Install the converter only on a level and horizontal surface.
Ensure that access to the holes in the bottom of the cabinets is unobstructed. Remove the
guard covers.
Mounting hardware
To screw the transport units together, you will need the following mounting hardware:
● Self-adhesive sealing strips
● Hexagon nut M8
● Contact washers
● Threaded pin M8 x 15.5
SINAMICS GL150 6SL38502UM114PA0Z
Operating Instructions Rev.201910281441 EXAMPLE
Set screws and
headless screws
nm
1.0
1.3
1.8
-
-
-
base units are screwed together.
5.4 Screwing the transport units together
Head screws with
in - lb
nm
8.6
2.5
11.5
3.0
15.9
3.9
-
4.8
-
-
-
-
Head screws with
slit
hexagon profile
in - lb
nm
22.1
2.5
26.6
3.5
34.5
7.2
42.5
13
-
18
-
30
Mounting
in - lb
22.1
31.0
63.7
115
159.3
265.5
69