Description
3.6 Description of options
3.6.6

Can Bus interface (option G20)

The standard version of the drive is equipped with a PROFIBUS interface (slave).
Communication Boards CBC10 and CBE20 are used to link the drive to the CANopen bus
system.
For more information about communication modules, see document "Supplementary
component descriptions".
3.6.7

Modbus Plus interface (option G21)

Using the Anybus X-Gateway communication module, the converter can be connected to the
Modbus Plus third-party bus system.
3.6.8

Modbus RTU Slave interface (option G22)

Using the Anybus X-Gateway communication module, the converter can be connected to the
Modbus RTU third-party bus system.
3.6.9

DeviceNet interface (option G23)

Using the Anybus X-Gateway communication module, the converter can be connected to the
DeviceNet third-party bus system.
The standard version of the drive is equipped with a PROFIBUS interface (slave). The "Anybus-
X-Gateway" supplied by HMS Industrial Networks is used to link the drive to the third-party
bus system. The X gateway is connected to the CU320 Control Unit using a PROFIBUS cable.
The option is supplied with a null modem cable for configuring the X gateway. The gateway is
preconfigured to 20 bytes of I/O data. The data size is changed via the configuration interface
from a PG/PC (standard PC tool "Windows Hyper Terminal").
Use the "NetTool" supplied by HMS Industrial Networks to configure PROFIBUS. The NetTool
is not included in the scope of supply.
3.6.10

Teleservice connection TS Adapter II analog modem (option G25)

With this option, a teleservice connection is available via the TS Adapter II of the analog modem.
3.6.11

Teleservice connection TS Adapter II ISDN modem (option G35)

With this option, a teleservice connection is available via the TS Adapter II of the ISDN modem.