Diagnostics
3.1 Diagnostics via LEDs
3.1.3.3

Meaning of LEDs on the Sensor Module Cabinet-Mounted SMC30

Table 3- 35
Meaning of LEDs on the Sensor Module Cabinet SMC30
LED
Color
RDY
-
READY
Green
Orange
Red
Green/
red
Green/
red
Green/
orange
or
Red/
orange
OUT > 5 V
-
Orange
208
Status
Off
Electronics power supply is missing or outside permissible
tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-
light
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
At least one fault is present in this component.
light
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Flashing
Firmware is being downloaded.
0.5 Hz
Flashing
Firmware download is complete. Wait for POWER ON.
2 Hz
Flashing
Component recognition via LED is activated (p0144).
light
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
Off
Electronics power supply is missing or outside permissible
tolerance range.
Power supply ≤ 5 V.
Continuous
Electronics power supply for encoder system available.
light
Power supply > 5 V.
Important:
Make sure that the connected encoder can be operated
with a 24 V power supply. If an encoder that is designed
for a 5 V supply is operated with a 24 V supply, this can
destroy the encoder electronics.
Description, cause
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Remedy
Remedy and
acknowledge fault
Carry out a POWER
ON