Ch Rate Alarm Upper/Lower Limit Value - Mitsubishi MELSEC Q Series User Manual

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.19 CH
rate alarm upper/lower limit value (buffer memory addresses 122 to 137:
Un\G122 to Un\G137)
3 - 64
(1)
Set the varying rate range of the digital output value for each channel.
(2)
To make the setting valid, the operating condition setting request (Y9) must be
turned ON/OFF. (Refer to Section 3.3.2.)
(3)
The setting range is -65536 to 65535 (-6553.6 to 6553.5%). Set the value in
0.1%/s increments.
Example) When setting the rate alarm upper limit value to 30%/s, store 300 into
the buffer memory.
(4)
Refer to Section 3.2.4 for details of the rate alarm.
POINT
The channel where the value outside the above setting range has been written
results in an error, the error code is stored into the Error code (buffer memory
address 19: Un\G19), the error flag (XF) turns ON, and the rate alarm is executed
at the pre-error setting.
MELSEC-Q
3 - 64