Ch[ ] Rate Alarm Warning Detection Period (Un\G126 To Un\G133); Ch[ ] Rate Alarm Upper/Lower Limit Values (Un\G134 To Un\G149) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.22

CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)

The number of conversion periods to check a change in measured temperature values is
set for each channel. (Refer to Section 3.2.4)
(1) Setting methods
(a) For use of the rate alarm, change the setting value.
(b) Set the number of conversion periods in buffer memory.
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "0".
POINT
3.4.23

CH[ ] Rate alarm upper/lower limit values (Un\G134 to Un\G149)

A scaling range of measured temperature values is set for each channel in units of
0.1
.(Refer to Section 3.2.4)
(1) Setting methods
(a) For use of the rate alarm, change the setting value.
(b) Set the range in buffer memory.
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "0".
• Settable range: 1 to 6000(times)
(1) When a value out of the above setting range is set, an error (error code: 70 )
occurs on the corresponding channel. Then, the following occurs.
• Error code (71 ) is stored into the Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.
(2) Set "Enable" in Warning output enable/disable (Un\G46). When "Disable" is
set, the settings of CH
Un\G133) is ignored.
• Settable range:-32768 to 32767
3.4.22 CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)
Rate alarm warning detection period (Un\G126 to
3.4 Buffer Memory
1
2
3
4
5
6
7
8
3
- 57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx configurator-tiQ68td-g-h02

Table of Contents