Auto Refresh Settings - Mitsubishi MELSEC Q Series User Manual

Channel isolated high resolution analog-digital converter module / channel isolated high resolution analog-digital converter module (with signal conditioning function)
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5 UTILITY PACKAGE (GX Configurator-AD)

5.5 Auto Refresh Settings

5 - 16
[Purpose]
Configure the A/D converter module's buffer memory for auto refresh.
[Operating procedure]
1
"Start I/O No.
"
1: Enter the start I/O No. in hexadecimal.
[Setting screen]
[Explanation of items]
(1) Items
Module side Buffer size
Module side Transfer word
count
Transfer direction
PLC side Device
"Module type"
"Module model name"
: Displays the size of the buffer memory for the
setting item that can be transferred (fixed at
one word).
: Displays the number of words to transfer the
CPU device from the head device (fixed at
one word).
: " " indicates that data is written from the
device to the buffer memory.
" " indicates that data is read from the buffer
memory to the device.
: Enter a CPU module side device that is to be
automatically refreshed.
Applicable devices are X, Y, M, L, B, T, C,
ST, D, W, R, and ZR.
When using bit devices X, Y, M, L or B, set a
number that can be divided by 16 points
(examples: X10, Y120, M16, etc.)
Also, buffer memory data are stored in a 16-
point area, starting from the specified device
number. For example, if X10 is entered, data
are stored in X10 to X1F.
MELSEC-Q