APPENDIX
Appendix 1.1 G(P).OFFGAN
Internal device
Set data
(System, user)
Bit
(S)
[Instruction
symbol]
G.OFFGAN
GP.OFFGAN
Set data
Un
Start I/O number of the module
Mode switching
0: Switching to normal mode
(S)
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to offset/gain
setting mode".
APP
APP -2
Switches the mode of the A/D converter module. (Normal mode to offset/gain setting
mode, offset/gain setting mode to normal mode)
Link direct device
File
register
Word
[Execution
condition]
Command
Command
Description
(1) Function
Switches the mode of the A/D converter module.
• Normal mode to offset/gain setting mode (the offset/gain setting mode flag (XA)
turns ON)
• Offset/gain setting mode to normal mode (the offset/gain setting mode flag (XA)
turns OFF)
POINT
(1) When the offset/gain setting mode is switched to the normal mode, Module
ready (X0) turns from OFF to ON.
Note that initial setting processing will be executed if there is a sequence
program that makes initial setting when Module ready (X0) turns ON.
(2) When the offset/gain setting mode is switched to the normal mode, the Q64AD-
GH holds the previous operation condition and resumes operation
automatically under the previous operation condition.
(3) When one mode is switched to the other (the normal mode is switched to the
offset/gain setting mode or the offset/gain setting mode is switched to the
normal mode), the Q62AD-DGH suspends A/D conversion and switches OFF
the power supply to the 2-wire transmitter.
To resume A/D conversion and power supply to the 2-wire transmitter, turn ON
the operating condition setting request (Y9) after the mode is switched to the
normal mode.
(2) Operation error
No errors.
Usable devices
Intelligent
J \
function
module
Bit
Word
U \G
Set data
MELSEC-Q
Index
Constant
register
Z
K, H
$
G.OFFGAN
Un
GP.OFFGAN
Un
Setting range
0 to FE
Binary 16 bits
H
0 ,1
Binary 16 bits
Other
(S)
(S)
Data type
APP -2